AAECU AlarmLine II Analogue EN Control Unit
Interface & Programming
The AAECU provides LED indications as well as a LCD. Internal
pushbuttons allow for easy configuration without the need for a PC.
Configuration via PC is also supported via a USB connection and the
optional configuration software AAECU-PCC.
Pre-Alarm and Alarm thresholds can be set through simple menu
options. Initial set-up is done by measuring and entering the calibration
resistance of the sensor cable, as well as the 3 letter cable parameter
identifier.
Volt free changeover contacts are provided inside the control unit for
Pre-Alarm and Alarm signaling to a main fire alarm control panel or
BMS system. A failsafe opto-isolated phototransistor fault output is
also provided.
No user controls are provided on the control unit. An isolated input is
provided enabling remote reset functionality.
Operation
As well as monitoring the LHD sensor cable for changes in
temperature, the control unit also monitors for open and short circuit
faults along the cable ensuring notification if the cable becomes
damaged.It is fitted with its own internal temperature monitor and
should the temperature within the controller enclosure reach 100°C
(212°F), an alarm will be signaled.
Each control unit may have up to 500m (1640ft) of LHD sensor cable
connected to it, acting as a single detection zone.
Details
The AAECU is supplied with an End-Of-Line unit (AAECU-EOL)
included. The End-Of-Line unit (AAECU-EOL) is also available
separately as a spare part.
A junction box (AAECU-JUN) is also available separately, if two pieces
of cable needs to be joint.